TM0110 Page 1 of 22 Issue 1.00 SIRIUS II 2, 4 & 8 ZONE CONVENTIONAL FIRE ALARM CONTROL PANEL INSTALLATION, OPERATION AND MAINTENANC
TM0110 Page 10 of 22 Issue 1.00 CHAPTER 3 INSTALLATION AND COMMISSIONING 3.1 GENERAL Installation of the fire detection and alarm system must
TM0110 Page 11 of 22 Issue 1.00 Static discharges can be reduced by following these guidelines: 1. Always use conductive or anti-static container
TM0110 Page 12 of 22 Issue 1.00 last device in each of the zone wirings, end of line resistors across auxiliary alarm circuits and fire outputs. Con
TM0110 Page 13 of 22 Issue 1.00 polarised. Non-polarised sounders will show a sounder fault. The most common sounders are bells and electronic soun
TM0110 Page 14 of 22 Issue 1.00 Figure 4: External Connections
TM0110 Page 15 of 22 Issue 1.00 3.4 COMMISSIONING CAUTION The control panel may be damaged by removing and/or inserting cards, modules, or interc
TM0110 Page 16 of 22 Issue 1.00 Turn the mains supply off. Using the short lead supplied, connect the positive terminal of one battery to the nega
TM0110 Page 17 of 22 Issue 1.00 ZONE ONE MAN TEST The ZONE ONE MAN TEST function allows the engineer to test zone FIRE responses from one or more z
TM0110 Page 18 of 22 Issue 1.00 PANEL ALARM MODES The PANEL ALARM MODES function allows the engineer to configure the panel alarm circuits. When t
TM0110 Page 19 of 22 Issue 1.00 CHAPTER 4 MAINTENANCE 4.1 GENERAL Maintenance of equipment external to the control panel will be detailed in t
TM0110 Page 2 of 22 Issue 1.00 TABLE OF CONTENTS Chapter Page 1.0 Description 1.1 General Description 3 1.2 Display Panel 4 1.3
TM0110 Page 20 of 22 Issue 1.00 CHAPTER 5 SPECIFICATIONS AND DATA 5.1 WIRING SPECIFICATION All system wiring should be screened and installed
TM0110 Page 21 of 22 Issue 1.00 Power Supply Mains supply voltage 230V AC +/- 10% 50/60 Hz Internal power supply 28V DC Nominal Output Voltage r
TM0110 Page 22 of 22 Issue 1.00 Maximum total sounder load Up to 500 mA each circuit (limit to 1A total) Maximum cable length per circuit 450 met
TM0110 Page 3 of 22 Issue 1.00 CHAPTER 1 DESCRIPTION 1.1 GENERAL DESCRIPTION Sirius II is a conventional fire alarm control panel designed to
TM0110 Page 4 of 22 Issue 1.00 1.2 DISPLAY PANEL All indications and controls are available via the Sirius II display panel (Figure 2). This inco
TM0110 Page 5 of 22 Issue 1.00 FIRE ALARM The red FIRE ALARM light comes on when any zone is in a fire alarm condition. This light flashes 1 secon
TM0110 Page 6 of 22 Issue 1.00 The following controls are available in Access Level 2: SILENCE / RESOUND ALARMS If the panel has a zone fire state,
TM0110 Page 7 of 22 Issue 1.00 1.5 EN 54 OPTIONAL FUNCTIONS WITH REQUIREMENTS The panel has the following optional functions: • Output to fire a
TM0110 Page 8 of 22 Issue 1.00 CHAPTER 2 OPERATION 2.1 GENERAL Under normal operating conditions, the green POWER ON light is on and the zone
TM0110 Page 9 of 22 Issue 1.00 2.4 DISABLEMENTS The disablement function allows the operator to disable several panel functions. The ZONE